Touch@Glass RFID reader

contactless access by card or tag

1- to 4-module, with custom graphic design

1-module2-module3-module4-module
Touch@Glass RFID reader

Touch@Glass RFID reader

A module for contactless identification by card or tag. It is used for access control, attendance and activating building functions. It reads Mifare cards and NFC tags already in use on the premises.

It fits in as one of the switch positions; no separate reader is needed on the wall. It is a member of the Touch@Glass family. It combines with either Touch@Glass or Touch@Glass EVO switches.

CARD OR TAG

RFID/NFC card or tag

Contactless RFID/NFC identification at 13.56 MHz, reading distance up to 50 mm.

LOCK OUTPUTS

Outputs for lock and signalling

Two universal inputs and five DO/PWM outputs for an electric lock, signalling or lighting.

Key features

  • The Touch@Glass RFID reader is a wall-mounted device for contactless identification of people using RFID/NFC cards and tags (13.56 MHz). It is typically used for access control, attendance tracking and activation of building functions — in combination with the TECO Foxtrot control system.
  • The StrongLink SL031 reader with a built-in antenna reads Mifare 1k / 4k / UltraLight and NFC NTAG203 tags; reading distance is up to 50 mm. The unique card UID is passed to the superior system; the full command set is available through the RFIDLib library (Mosaic).
  • The module operates as a node on the TECO CIB bus; both power and communication are provided by a single bus cable.
  • 2 universal DI/AI inputs are available (temperature sensors, potential-free contacts, balanced intruder-alarm loops with tamper) together with 5 DO/PWM outputs — e.g. for switching an electric lock, signalling or lighting.
  • Design and functions customized to the interior; user-replaceable glass.
  • Touch@Glass is available in 1-module (94×94 mm), 2-module (94×165 mm), 3-module (94×236 mm) and 4-module (94×307 mm) configurations. The front panel consists of 4 mm safety tempered glass with custom printing.

Technical specifications

Parametr1-module2-module3-module4-module
RFID reader
Frequency13.56 MHz
Supported tagsMifare 1k / 4k / UltraLight, NFC NTAG203
Reading distanceup to 50 mm (depending on tag type)
Transmitted datatag UID (commands via the RFIDLib library)
Inputs and outputs
Universal inputs2× DI/AI — digital / balanced intruder-alarm loop (tamper) / analog (Pt1000, Ni1000, NTC 12k, KTY, 0÷100 kΩ, 0÷2 V)
Outputs5× DO (4× optionally PWM 100 Hz÷2 kHz), DO5 galvanically isolated; +22 V OUT
Communication
Communication busTECO CIB (Foxtrot 2 / CIB master CF-214x); handled from Mosaic (RFIDLib)
Power supply
Supply voltagefrom TECO CIB bus 24 V or 27 V DC
Current / power inputtyp. 20 mA / 0.5 W, max. 80 mA / 2.2 W
Operating conditions
Temperature rangeoperating 0 °C to +50 °C, storage −25 °C to +85 °C
Protection ratingIP40 front, IP20 rear
C-WG-0205S control module0 °C to +55 °C, protection rating IP10B
Installationin a back box with a minimum depth of 30 mm(45 mm recommended)
Dimensions and weight
Overall dimensions94×94×28 mm94×165×28 mm94×236×28 mm94×307×28 mm
Total weight157 g278 g399 g520 g
Glass thickness and type4 mm, safety tempered glass

The datasheet (PDF) is the binding document for project planning and ordering. The information on this page is an informative summary.

Kombinace

Under one glass with other modules

  • Can be combined under one glass: the RFID reader with a Touch@Glass or Touch@Glass EVO switch and with the CO₂ module
  • Cannot be combined: the RFID reader with both product lines at once
  • Standalone only: fingerprint reader (1 module, 94 × 94 mm)

Download the datasheet

Downloads
Next step

Add the Touch@Glass RFID reader to your switch

Choose the modules, glass, design and button labels. We will send you the price list by email.