For partners

Touch@Glass for partners

For Tecomat Foxtrot system integrators, architects and design engineers.

Two-module Touch@Glass switch with two segment displays, brushed metal design glass

Touch@Glass | Touch@Glass EVO

CIB bus, 1 to 4 modules under one glass.

Touch@Glass

Touch buttons with RGB LEDs and a segment display; temperature and humidity sensor as standard, can also be ordered without sensors.

Touch@Glass EVO

The new generation: touch buttons with RGB LEDs and a dot-matrix LED display, built-in temperature and humidity sensor; optional ambient light and proximity sensor and haptic feedback.

Overview

Bus

CIB of the Tecomat Foxtrot system, power and data over a single cable

Power supply

24 V or 27 V DC from the CIB bus

Consumption

30–65 mA per switch module, see the table below

Sizes

1 to 4 modules side by side or one above the other; module 94 × 94 mm; vertical version without display

Series

Touch@Glass (segment display) or Touch@Glass EVO (dot-matrix display); they cannot be combined under one glass

Modules

CO₂ and the RFID reader can be added under one glass; fingerprint reader standalone only (1 module)

Back box

min. 30 mm (45 mm recommended); fingerprint reader min. 45 mm (60 mm recommended)

Glass

4 mm safety tempered, printed to the project design, replaceable; automatic calibration within 40 seconds after the glass is removed

Ordering

from Teco a.s. via the B2B catalog

Documentation

datasheets at /en/downloads/, design in the configurator

Wiring

  • Direct connection to the CIB bus, with no converter and no extra app.
  • Touch@Glass terminal block: +CIB−, AI1, GND, AI2, +24V, GND, DO; CIB address on the label.
  • Can be combined under one glass: a Touch@Glass switch or a Touch@Glass EVO switch, the CO₂ module and the RFID reader, 1 to 4 modules in total.
  • Cannot be combined: Touch@Glass and Touch@Glass EVO under one glass.
  • Standalone only: fingerprint reader (1 module, 94 × 94 mm), on the CIB bus alongside the other switches.
Two wiring diagrams on the CIB bus: at the top Touch@Glass with a segment display, at the bottom Touch@Glass EVO with a dot-matrix display; both with the CO₂ module, RFID reader and fingerprint reader

Power supply and consumption

module

power supply

rated current

Touch@Glass / EVO, 1 module

24 / 27 V DC from CIB

30–65 mA

2 modules

60–130 mA

3 modules

90–195 mA

4 modules

120–260 mA

CO₂

max. 30 mA, 2 mA idle

fingerprint reader

max. 30 mA, 2 mA idle

RFID reader

typ. 20 mA, max. 80 mA

CIB bus (according to TECO documentation):

Units per branch

max. 32; a switch with 2, 3 or 4 modules takes up 2, 3 or 4 addresses

Line current

max. 1 A (CF-2141, CF-2142, CP-2000, C-BS-0001M bus separator); the internal masters CP-2005, CP-2007, CP-2080, CP-2090, CP-2091 supply only up to 100 mA, use the C-BS-0001M bus separator for higher consumption

Voltage

24 V DC without backup / 27.2 V DC with backup, tolerance 20.4–30 V

Length

max. 500 m from the master

Topology

any (line, star, branches), no ring, no termination

Cable

twisted shielded pair, e.g. J-Y(St)Y 1×2×0.8 (conductor diameter 0.8 mm)

Foxtrot 2 branches

CP-2000: 2 internal lines; CP-2005/2007/2080/2090/2091: 1 internal line; further branches via CF-2141 / CF-2142 (max. 7 modules, up to 14 lines)

  • RFID reader: handled from Mosaic.

Mosaic

In Mosaic, the switch is added in the I/O Configurator as a CIB unit. The data structures are the same as in the Touch@Glass and Touch@Glass EVO datasheets.

input structure

description

DI

state of binary inputs DI1 and DI2, short and long pulse on the input

AI_STAT

status byte of the analog inputs and the internal thermometer and hygrometer (range overflow, measurement validity)

AI1, AI2

analog input value [°C], [kΩ], [mV]

GLASS.BTN

current state of buttons 1 to 6

GLASS.BTNs.CLICK

short press of buttons 1 to 6

GLASS.BTNs.PRESS

long press of buttons 1 to 6

GLASS.VALUE

EVO: light intensity in lux (if the sensor is fitted)

GLASS.STAT

EVO: proximity sensor active, sensor and display communication errors

THERM

temperature [°C]

RH

humidity [%]

output structure

description

GLASS.CONT

module control word: display on, binary output DO1 (max. 30 V / 3 A); EVO additionally haptic feedback, WiFi and firmware upload

GLASS.LED

RGB LED at each button (blue, red, green)

DISPA

value to show on the display, range –32,768 to 32,767

ZONE, ICONS

EVO: number formatting and predefined texts on the dot-matrix display

DLIGHT, BLIGHT

display and LED brightness [%]

  • On the CO₂ module, GLASS.VALUE carries the CO₂ concentration in ppm.
  • Optional external temperature sensor (Pt1000, Ni1000, NTC 12k, KTY81-121) or measurement of resistance up to 100 kΩ and voltage 0–2 V on the AI inputs.

Dimensions and installation

modules

glass size

buttons

1

94 × 94 mm

6

2

165 × 94 mm

12

3

236 × 94 mm

18

4

307 × 94 mm

24

  • Orientation: Switches can be mounted horizontally or vertically; the vertical version has no display. You choose the orientation in the configurator. For the vertical version, the dimensions in the table are the height; the width is 94 mm.
  • Back box: min. 30 mm, 45 mm recommended. Fingerprint reader: min. 45 mm, 60 mm recommended.
  • Protection rating: IP40 front, IP20 rear.
  • Operating temperature: 0 to +50 °C, humidity max. 80%.
  • Replacing an existing wall switch: possible where there is a CIB bus and a box at least 30 mm deep.
  • Installation instructions and drawings: in the datasheets at /en/downloads/.
Glass sizes one above the other: 1 module 94 mm, 2 modules 165 mm, 3 modules 236 mm, 4 modules 307 mm wide (high for the vertical version); the other dimension is always 94 mm

Graphics and glass

Glass

4 mm safety tempered, abrasion-resistant

Surface

smooth · satin matte · with recesses (only 1–2 modules fitted exclusively with buttons; not with CO₂, RFID or fingerprint reader)

Graphics

design from a collection, custom pictograms, room labels, logo; design and printing included in the price of the glass

Glass replacement

for button modules no service visit needed, automatic calibration within 40 seconds after the glass is removed; for the fingerprint reader and RFID reader by a professional service technician

Configurator

  • Modules, glass, design and button labels.
  • The design is sent to TECO as an inquiry.
Open the configurator
Design of a two-module Touch@Glass switch in the configurator: anthracite glass, icons for lights, shading and temperature

Specification text

For inserting into a technical report or bill of quantities. Adjust the values in brackets.

Wall-mounted glass smart switch Touch@Glass [EVO] for the CIB bus of the Tecomat Foxtrot system, [1/2/3/4]-module, glass size [94/165/236/307] × 94 mm, 4 mm safety tempered glass printed to the project design, [6/12/18/24] touch buttons with RGB LEDs, [segment/dot-matrix] display, [internal temperature and humidity sensor], power supply and communication from the CIB bus 24/27 V DC, IP40 protection from the front, mounting in a flush-mounting box at least 30 mm deep (45 mm recommended). Supplier Teco a.s.

The configurator generates the assembly order code in the form C-WS-[buttons][surface][modules]R[-TG2]-[displays], for example C-WS-12S2R-TG2-M1W (two-module Touch@Glass EVO, satin matte glass, 12 buttons, one white dot-matrix display).

Ordering

Price list

Recommended retail prices by email.

Ordering

Teco a.s., B2B catalog and partner account.

Inquiry from the configurator

A design sent as an inquiry.

Sales representatives

Bohemia and Moravia.

Service

Technical Support

MICRONIC Přerov s.r.o., +420 773 768 693, podpora@micronic.cz

Warranty

24 months

Delivery time for glass with graphics

4 weeks

Replacement glass

including printing and custom graphic design: a price-list item by size (1–4 modules) and surface (smooth / satin matte / with recesses), ordered from TECO like any other item; glass with recesses only for 1- and 2-module switches fitted exclusively with buttons. For the fingerprint reader and RFID reader, the glass is fitted by a professional service technician.